Huafon ESS Technology Industrial Energy Storage System (33kW/92kWh)

use

  • Base shelter power outage backup
  • BCP measures for companies and public facilities
  • Private consumption of solar power generation
  • Demand Control Reduces Electricity Rates

feature

high power
It can be equipped with a maximum output of 33 kW and a storage battery capacity of up to 92 kWh.
Long life and low degradation
Battery capacity is 80% of initial maximum capacity while charging and discharging for 6000 cyclesnote (supplementary information) symbolHold above
*Usage environment 0.5C@25℃.
functionality
Our unique energy storage management system aggregates battery information at each hierarchical level, from the cell to the system level, and provides a variety of applications, including control from the EMS, enabling the status of the energy storage system to be checked at all times.

(technical) specification

ESSmodel (e.g. of a vehicle)IC1-3092-OD
AC side
(technical) specification
AC outputRated: 30kVA Maximum: 33kVA "Linked and stand-alone operation
conversion efficiency97.10%
Rated AC voltageThree-phase 200 V "with isolation transformer"
AC voltage rangeThree-phase 200V±10
Rated frequency50Hz or 60Hz "within ±0.1Hz"
Parallel operation of multiple unitsUp to 4 units can be operated in parallel
safeguardOvervoltage (OV) Undervoltage (UV) Overfrequency (OF) Underfrequency (UF)
Battery side
(technical) specification
cell typeLFP "Lithium iron phosphate
Standard installed capacityInitial battery capacity: 10.24 kWh x 9 units = 92.16 kWh total
Standard charge/discharge cycle6000 cycles: Initial battery capacity SOC: 80% min. 0.5C@25°C conditions
general
(technical) specification
cubicleStandard Specifications "Ordinance Conforming Equivalent"
External dimensionsW:1882㎜×D:1206㎜×H:1855㎜
weightApprox. 1800Kg
Protection classEquivalent to IP55
Operating temperature-20°C to 45°C "Output suppression above 45°C
communication system4G RS485 Ethernet